Output Voltage
|
46 - 57 V
|
Power (max.)
|
2400 W
|
Output Current (max.)
|
18.2 A (XR04.48), 35 A (XR08.48), 45 A (XPGe12.48)
|
Rectifier Types
|
XR04.48 / XR08.48 / XPGe12.48
|
DC DISTRIBUTION
|
Battery Breakers (max.)
|
1 (Sizes: 40 A, 50 A, 65 A)
|
Load Breakers (max.)
|
4 (Sizes: 1 A, 4 A, 5 A, 7.5 A, 10 A, 15 A, 20 A, 25 A, 30 A)
|
INPUT
|
AC Input Connections
|
100 - 250 VAC, 1x Single-phase or 2x Single-phase
|
Frequency
|
50 - 60 Hz
|
Input Current (max.)
|
16 A (Single-phase) 8 A (2x Single-phase)
|
Power Factor
|
> 0.98 (typical)
|
MONITORING AND CONTROL
|
Controller
|
ACC Extended / PCC
|
Local Interface
|
4 x 20’ LCD, 4-key menu, USB / RS232
|
Remote Interface
|
Ethernet / Modem using PowCom™ software package
|
LED Indications
|
Green LED - System ON; Yellow LED - Message(s); Red LED - Alarm(s)
|
Analogue Inputs
|
12x Multi-Purpose voltage inputs (0 – 100 VDC)
|
Analogue Outputs
|
4x Potential free alarm relays (C, NC, NO)
|
Digital Inputs
|
2x, Logic 0: V < 10 VDC, Logic 1: V > 12 VDC
|
Digital Outputs
|
2x (open collector type)
|
Temperature Measurement
|
2x Temperature probe (Battery, Ambient)
|
BATTERY MANAGEMENT
|
Symmetry Inputs
|
Max. 3
|
Programmable LVD
|
Yes
|
Temperature Compensation
|
Yes
|
CONNECTIONS
|
Battery connections
|
Stripped cable, max.16 mm2, spring type connector
|
AC connection
|
Stripped cable with ferule, max. 2.5 mm2, screw type connector
|
Load breaker connections
|
Stripped cable with ferule, max. 4 mm2, screw type connector
|
Alarm connections
|
Stripped cable with ferule, max. 1.5 mm2, screw type connector
|
COMPLIANCE
|
EMC
|
ETSI EN 300 386 V.1.5.1, EN 55022, EN 55024, EN 61000-4
|
Safety
|
EN 60950-1, UL/CSA60950-1+A1, IEC60950 2nd+A2
|
ENVIRONMENTAL
|
Operating Temperature
|
-40 ºC to +75 ºC, derating over 55 ºC
|
Storage Temperature
|
-40 ºC to +85 ºC
|
MECHANICAL
|
Dimensions ((WxHxD)
|
480 x 44.45 x 280 mm
|
Weight - empty power shelf - fully equipped
|
3.3 kg
6.5 kg
|
Mounting Options
|
19” / ETSI / Mid-mount
|